Pepperl+fuchs Podcasts

AS-Interface TechTalk Podcast 49

Informações:

Sinopse

Ground faults for AS-Interface must be avoided. No news here. In this case we were confronted with an AS-Interface system composed of three networks and suddenly all three networks reported a ground fault. How is that possible?  Systematic troubleshooting makes it easy and fast to figure out what is going on. The second topic today deals with connecting two e-stops in series to a single safe input module. Everything worked until the installers tested an e-stop.  Now they were not able to restart. Strange?  Fortunately, there are LEDs on the safety modules to troubleshoot these kinds of situations.  -- When multiple AS-Interface networks are powered from one common power supply using power conditioners, ground faults on any of the three networks will feedback onto the other networks. We tell you how to go about determining where the issue is. -- Connecting multiple e-stops in series to one safety module is a common procedure.  But, the first contact of e-stop 1 must be connected in